Burglar Panel view

Arms and disarms a third-party burglar alarm panel.
Figure 183.   Burglar Panel view
Image

To access this view, click on a burglar panel link Image that is listed in the Burglar Panels tab under the Module Setup view. The burglar panel display name appears at the top of the view. The following control buttons display above the Burglar Panel tab.

  • Save is available when there are unsaved changes in the view. Click the button to save changes.
  • Base Reader Module button links to the Module Setup view.
Property Value Description
Out read-only Reports the current Panel Arm Relay Out state and status. The Arming In property controls the state, which is triggered only when the Arming In property value changes and the new value does not match the Panel Arm Status value.
Enabled true and false Turns the feature on (true) and off (false).
Relay Pulse Time up to 1 minute maximum Sets the time for the assigned relay output pulse to attempt to change the burglar alarm panel status.
Arming In Ref Chooser (defaults to none) Defines how to arm the panel.Image Schedule arming arms the burglar panel by assigning a schedule using this property.Image Intrusion Zone arming arms the burglar panel by assigning an access zone to the property.
Panel Arm Status Ref Chooser Assigns the status input for the burglar panel. The value of this input indicates the actual status of the burglar alarm. the system compares it to the Arming In property value to detect a match or mismatch condition.
Panel Arm Relay Ref Chooser Assigns the arming relay for the burglar panel. This relay momentarily energizes (for the Relay Pulse Time) the panel in an attempt to change the burglar alarm status to match the Arming In value.
Alarm Delay minutes and seconds (defaults to one minute) Defines a minimum amount of time to wait if a mismatch exists between the Arming In and Panel Arm Status. For example, when a Arming In value changes and a mismatch is detected, an alarm is generated only after the Alarm Delay time is exceeded.
Burglar panel Mismatch Alarm Class drop-down list Defines the alarm class to use for alarms generated as the result of a mismatch between Arming In and Panel Arm Status.