To access this view, click on a burglar panel link
that is listed in the Burglar Panels tab under the Module Setup view. The burglar panel display name appears at the top of the view. The following control buttons display above the Burglar Panel tab.
| Property | Value | Description |
|---|---|---|
| Out | read-only | Reports the current Panel Arm Relay Out state and status. The Arming In property controls the state, which is triggered only when the Arming In property value changes and the new value does not match the Panel Arm Status value.
|
| Enabled | true and false |
Turns the feature on (true) and off (false). |
| Relay Pulse Time | up to 1 minute maximum | Sets the time for the assigned relay output pulse to attempt to change the burglar alarm panel status. |
| Arming In | Ref Chooser (defaults to none) | Defines how to arm the panel. |
| Panel Arm Status | Ref Chooser | Assigns the status input for the burglar panel. The value of this input indicates the actual status of the burglar alarm.
the system compares it to the Arming In property value to detect a match or mismatch condition.
|
| Panel Arm Relay | Ref Chooser | Assigns the arming relay for the burglar panel. This relay momentarily energizes (for the Relay Pulse Time) the panel in an
attempt to change the burglar alarm status to match the Arming In value.
|
| Alarm Delay | minutes and seconds (defaults to one minute) | Defines a minimum amount of time to wait if a mismatch exists between the Arming In and Panel Arm Status. For example, when a Arming In value changes and a mismatch is detected, an alarm is generated only after the Alarm Delay
time is exceeded.
|
| Burglar panel Mismatch Alarm Class | drop-down list | Defines the alarm class to use for alarms generated as the result of a mismatch between Arming In and Panel Arm Status.
|