IP Port tab

This tab configures the BACnet/IP link layer used by the controller, providing that the Enabled property (in BACnet Network tab) is set to true.
Figure 207.   IP Port tab
Image

To access this view, click Controller Setup > Remote Devices > BACnetNetwork, followed by clicking the IP Port tab.

Properties

Property Value Description
Enabled true or false Turns the feature on (true) and off (false).
Status read-only Reports the condition of the entity or process at last polling.

{ok} indicates that the entity is licensed and polling successfully.

{down} indicates that the last poll was unsuccessful, perhaps because of an incorrect property.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem.

Depending on conditions, multiple status flags may be set including {fault} and {disabled}, combined with {down}, {alarm}, {stale}, and {unackedAlarm}.

Fault Cause read-only Reports the reason why a network, component, or extension is in fault. Fault Cause is blank unless a fault exists.
Network Number number from 1 to 65534; default value is -1 (inoperative) Specifies a unique network number across the entire BACnet internetwork for the BACnet/IP network. The .
Adapter NET1 (default) or NET2 Specifies which of the two physical Ethernet ports on the controller is used for BACnet/IP communications.
UDP Port port number; defaults to 0xBAC0 (decimal 47808) Specifies the UDP (user datagram protocol) port used by BACnet/IP. You can specify another port, if needed (say an existing BACnet/IP network is using another UDP software port).
IP Device Type drop-down list: BACnet device (the default), a BBMD (BACnet Broadcast Management Device) or BACnet Foreign Device. Defines the type of BACnet/IP device Generally, the default Standard should by used.
Bbmd Address number Sets the Bbmd (BACnet Broadcast Management Device) address. This address is only required when the system is being used as a BACnet Broadcast Management Device.