Add New (or edit) Intrusion Display view

This view creates a new intrusion display. A similar view edits existing intrusion displays.
Figure 281.   Add New Intrusion Display view
Image

You access this view by clicking Controller (System) Setup > Intrusion Setup > Intrusion Displays, followed by clicking the Add button (Image).

To edit an existing intrusion display, double-click the display row in the table.

Links

A Save button and an Intrusion Displays view link are located directly above a Display Name property at the top of the view.

Intrusion Display properties

These properties configure the new intrusion display.

Property Value Description
Default Message text Defines what to display on the default Time screen, at the top of the display.
SmartKey Device drop-down list (defaults to None) Lists the SmartKey devices that are available to be assigned to the current intrusion display.
 
NOTE: This list displays as a read-only field in the Add New Intrusion Display view, but is available in the Edit Intrusion Device view.
 
Scroll Start Delay minutes, seconds, and milliseconds Sets the amount of time before a text line on the display starts scrolling. (When a text field is too long (wide) to fit completely in the display, it scrolls continuously across the screen, horizontally.)
Scroll Column Delay minutes, seconds, and milliseconds Specifies how fast scrolling display text moves across the display screen.
Change Delay minutes, seconds, and milliseconds Specifies how long to pause between messages when there is more than one message to display, and the desired time to wait between scrolling each sequential message.
Inactivity Time minutes and seconds Defines when to revert to the default menu and low-power mode if there is no activity at the SmartKey device for a certain amount of time.
Status Beep true or false Turns on (true) and off (false) a single beep at the SmartKey device when the intrusion zone status changes from armed to disarmed status.
Arming Pin Required true or false Requires (true) or does not require (false) a valid PIN when arming an intrusion zone.
Status Pin Required true or false Requires (true) or does not require (false) a valid PIN when displaying intrusion zone status using the SmartKey device.
Point Display drop-down Determines how to display any fault message on the display screen (and virtual display) when initiating an arming action using the SmartKey device.No Path displays the fault message without identifying the point. For example: Supervisor Fault DetectedNormal Path displays the fault message followed by the point identity. For example: Door1.Sensor.Supervisor Fault DetectedReverse Path displays the point identity followed by the fault message. For example: 
Supervised Fault Detected.Sensor.Door1
Default Page drop-down list Assigns a default display page for the SmartKey device. This page opens at the end of the Inactivity Time and is, typically, the initial screen that a user sees at the SmartKey device.Summary sets the Summary screen as the default screen. This screen displays zone identification and status information about the assigned intrusion zone as well as a menu of actions to control arming and disarming the zone. Time sets the Time screen as the default screen. This screen displays the default message as well as the current date and time. Pressing the SmartKey device F1, F2, or F3 changes the display to the Summary screen.
In Alarm Beep true or false Turns on (true) and off (false) a single beep when there is an intrusion zone alarm.
In Alarm Max Beep hours, minutes, seconds Defines how long the alarm beep lasts when In Alarm Beep is set to true.