To access this view, click , click on the Add button (
) or double-click an existing count relay to open an existing alarm-count-to-relay record.
If you are editing an existing record, the alarm-count-to-relay configuration name displays in the title of the view over the Save, Test, and Alarm Count To Relays links.
You can move among tabs without losing unsaved data, however, you must click the Save button before leaving the view or data is lost and no new record is added to the database.
The Test button causes the relay to cycle on and off. The Alarm Count To Relays link returns to the Alarm Count To Relays view.
| Property | Value | Description |
|---|---|---|
| Relay Out | read-only | Displays the current relay output value and status. |
| Timer | minutes seconds milliseconds | Sets the active duration of the relay output. |
| Alarm Count Type | drop-down list | Defines the type of alarm states that are counted and used to generate an action. Unacked Alarm Count counts alarms that have not been acknowledged. Open Alarm count counts alarms that have not been cleared from the console. In Alarm Count counts alarms that have not yet returned to normal. Total Alarm Count counts all alarms regardless of state.
|