Access Network view and tab

This view displays values that apply to all devices assigned to the access network.
Figure 189.   Access Network view
Image

This view opens when you click Controller Setup > Remote Devices > Remote Modules the Access Network Setup menu item under the .

Clicking the Save button applies any changes.

Property Value Description
Status read-only Reports the condition of the entity or process at last polling.

{ok} indicates that the entity is licensed and polling successfully.

{down} indicates that the last poll was unsuccessful, perhaps because of an incorrect property.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem.

Depending on conditions, multiple status flags may be set including {fault} and {disabled}, combined with {down}, {alarm}, {stale}, and {unackedAlarm}.

Fault Cause read-only Reports the reason why a network, component, or extension is in fault. Fault Cause is blank unless a fault exists.
Enabled true or false Turns the Access Network on (true) and off (false).
Health read-only Reports the status of the network or component. This advisory information, including a time stamp, can help you recognize and troubleshoot network problems but it provides no direct network management controls.
Validation Timeout minutes and seconds Defines the maximum time allowed to receive a badge validation. If validation fails to occur within this time, the system may generate a validation-timeout-expired alarm.
 
NOTE: A validation timeout alarm may be caused if a validation cache fault occurs, or if the cache is still initializing.
 
Show Results Time minutes and seconds Defines the time that the (normally false) valid or invalid status remains true after a card is swiped.
Keypad Entry Time minutes and seconds Specifies a maximum amount of time after a badge swipe that is allowed before keypad entry must be completed.
Cut Value voltage (V) Defines a value for the cut voltage parameter on the network.
Open Value voltage (V) Defines a value for the open voltage parameter on the network.
Closed Value voltage (V) Defines a value for the closed voltage parameter on the network.
Alarm Source Info Ref Chooser Expands to display alarm class properties, which are documented in the System Setup-Alarm Setup topic.