You access this view from the main menu by clicking , followed by double-clicking the NrioNetwork driver, selecting and double-clicking a module, clicking the Point Manager link, followed by clicking the hyperlink to the right end of the Voltage Input point.
The Out section of the Voltage Input tab reports the current value of the proxy point and its status.
Facets determine how a point’s value displays in the station. Voltage Input facets include voltage numbers and decimal precision.

This Edit window opens when you click the Edit button.
| Property | Value | Description |
|---|---|---|
| Quantity | ||
| max | number | Defines the maximum voltage value. |
| min | number | Defines the minimum voltage value. |
| precision | number | Defines the number of decimal places allowed. |
| units | defaults to Volts | Configures the default unit. |
These properties configure the proxy point extension.

In addition to the standard properties (Status, Fault Cause, and Enabled), these properties support the voltage proxy extension.
| Property | Value | Description |
|---|---|---|
| Conversion | drop-down list, defaults to Default |
Defines how the system converts proxy extension units to parent point units.
|
| Tuning Policy Name | drop-down list, defaults to Default Policy.
|
Identifies the assigned tuning policy. During polling, the system uses such collections of rules to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only | Reports the last value read using device facets. |
| Write Value | read-only | Reports the last value written using device facets. Applies only to writable points. |
| Poll Frequency | drop-down list, defaults to Normal |
|
| Instance | number | Defines the point’s I/O terminal address based on its hardware type. If duplicated (same instance as same hardware type, same board), the point reports a fault status. |
| Ui Type | read-only | Identifies the Nrio Universal Input point type: Resistive Input, Boolean Output, etc. |
These properties configure the linear calculation that yields the Out value.

| Property | Value | Description |
|---|---|---|
| Scale | number, defaults to 1.0 | Part of a formula for converting voltage to something other than Volts. This also involves changing value facets. |
| Offset | positive or negative number, defaults to 0.0 | Works with Scale to convert voltage to something other than Volts. This property is useful to compensate for signal error introduced by sensor
wiring resistance.
|
| Units, Quantity | drop-down list | |
| Units | drop-down list | Should be the same as the parent proxy point’s facets. |
| Fault Cause | read-only | Reports the reason why a network, component, or extension is in fault. Fault Cause is blank unless a fault exists. |