Purge Config window (simple)

This window provides properties for setting the maximum number and means for handling history records (capacity). You must be logged in as a user with the appropriate write permissions for the Purge Config button (Image) to display in the toolbar.
 
NOTE: Once history records have been purged, they cannot be retrieved unless they were previously backed up.
Figure 70.   Purge Config window in a remote controller station
Image

 
This window opens in a remote controller station when you click Reports, click one of the history reports, and click the Purge Config button (Image).
 
NOTE: The exact properties differ, depending on the type of history view associated with the Purge Config window.
 
Property Value Description
Capacity number Defines the maximum number of history records allowed in the associated history table. What happens when the record count reaches Capacity depends on the Full Policy setting.
Full Policy drop-down list Determines what happens when the history table reaches its maximum Capacity.Stop restricts the table to the Capacity. After reaching this number, the system ignores new records. Roll replaces the oldest records with newer records.