You access this from the Nrio Point Manager, Analog Points tab by clicking the hyperlink on a Resistive Input point.
Facets determine how a point’s value displays in the station. Resistive input facets include a minimum, maximum, and decimal precision.

The Edit window opens when you click the Edit button.
| Property | Value | Description |
|---|---|---|
| Quantity | drop-down list | Defines the formula. |
| Unit | defaults to ohm | Configures the default unit. |
| Max | number, defaults to Infinity | Defines the maximum ohm value. |
| Min | number, defaults to negative Infinity | Defines the minimum ohm value. |
| Precision | number, defaults to one | Defines the number of decimal places allowed. |
These properties configure the proxy point extension.

| Property | Value | Description |
|---|---|---|
| Status | read-only | Reports the condition of the entity or process at last polling.
{ok} indicates that the entity is licensed and polling successfully. {down} indicates that the last poll was unsuccessful, perhaps because of an incorrect property. {disabled} indicates that the Enable property is set to false. {fault} indicates another problem. Depending on conditions, multiple status flags may be set including {fault} and {disabled}, combined with {down}, {alarm}, {stale}, and {unackedAlarm}. |
| Fault Cause | read-only | Reports the reason why a network, component, or extension is in fault. Fault Cause is blank unless a fault exists. |
| Enabled | true or false |
Turns the feature on (true) and off (false). |
| Conversion | drop-down list, defaults to Default |
Defines how the system converts proxy extension units to parent point units.
|
| Tuning Policy Name | drop-down list, defaults to Default Policy.
|
Identifies the assigned tuning policy. During polling, the system uses such collections of rules to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only | Reports the last value read using device facets. |
| Write Value | read-only | Reports the last value written using device facets. Applies only to writable points. |
| Poll Frequency | drop-down list, defaults to Normal |
|
| Instance | number | Defines the point’s I/O terminal address based on its hardware type. If duplicated (same instance as same hardware type, same board), the point reports a fault status. |
| Ui Type | read-only | Identifies the Nrio Universal Input point type: Resistive Input, Boolean Output, etc. |
These properties configure the linear calculation that yields the Out value.

| Property | Value | Description |
|---|---|---|
| Scale | number, defaults to 1.0 | Part of a formula for converting temperature. This also involves changing value facets. |
| Offset | positive or negative number, defaults to 0.0 | Works with Scale to convert temperature.
|
| Units, Quantity | drop-down list | |
| Units | drop-down list | Should be the same as the parent proxy point’s facets. |
| Fault Cause | read-only | Reports the reason why a network, component, or extension is in fault. Fault Cause is blank unless a fault exists. |