Intrusion Zones tab, Intrusion Zone tab

This tab configures a new intrusion zone or updates an existing zone.

Property Value Description
Occupancy Count read-only Displays the number of personnel currently in the zone.
Occupied read-only true or false Indicates if the access zone is currently occupied.
Lock Down true or false (default) Enables and disables a lock down, which prohibits immediate access to the zone regardless of how the enforcement rules are configured. false allows normal operation. true disables (locks down) the zone.
Occupancy Criteria drop-down list Keeps track of who is in the zone:Any counts all personnel, including supervisors. Supervisors counts only supervisor personnel.
Passback Mode drop-down list Determines how to handle activity alerts. Off disables anti-passback. Soft grants access and generates an alarm. Hard denies access and generates an alarm.
Above High Threshold Enforcement drop-down list Specifies the type of enforcement to use when a high-threshold occupancy setting is exceeded. Off disables above-high-threshold enforcement. Soft allows access and generates an alarm. Hard denies access and generates an alarm.
At High Threshold Enforcement drop-down list Specifies the type of enforcement to use when a high-threshold-occupancy setting is met. Off disables enforcement. Soft grants access and generates an alarm.
Below Low Threshold Enforcement drop-down list Off disables below-low-threshold enforcement. Hard grants access and generates an alarm.
At Low Threshold Enforcement drop-down list Off disables below-low-threshold enforcement. Soft grants access and generates an alarm.
Supervisor Required Enforcement drop-down list Denies access to all non-supervisor persons unless a supervisor is already an occupant. Off disables the requirement for a supervisor. Soft requires a supervisor. Grants access even though a supervisor is not present but generates an alarm. Hard denies access when a supervisor is not present and generates an alarm.
Pending Time minutes and seconds Defines the time allowed for a second person to swipe a badge to prevent a threshold alarm. If a second badge is not swiped in the specified time, the system generates an occupancy alarm and may deny access.
Passback Timeout hour, minute, and second Specifies a time (timeout) after which a badge may be re-scanned at the reader without causing a passback alarm.
Reset Occupancy Enabled true or false (default) Clears the zone of people who did not scan their badges when they left the building. This prepares the zone so that people can enter again in the morning. One may want to reset occupancy at night or when you know no one is actually in the zone.
Reset Occupancy Time 12-hr. clock Defines a time to automatically reset occupancy and set the number of occupants to zero. The function is the same as clicking the Reset Occupants button.
High Threshold number (defaults to 100) Defines the maximum number of occupants allowed in an access zone.
Low Threshold number (defaults to -1) Defines the minimum number of occupants allowed in an access zone.