Relay Links tab

This tab manually assigns and unassigns output relays to the intrusion zone. This output relay is active whenever the intrusion zone is in an armed state.
Figure 261.   Relay Links tab
Image

This tab opens when you click Controller (System) Setup > Intrusion Setup > Intrusion Zones, double-click a zone in the table and click the Relay Links tab.

You add items to the currently displayed intrusion zone using the learn mode and the assign and unassign buttons.
  • Image Turn Off Relays manually turns off the selected output relay.

    Relay Links columns

    Column Description
    Display Name Provides the recipient’s name.
    Alarm Count Type Identifies the count type configured (in the Add New Alarm Count to Relay view) to activate the relay. Unacked Alarm Count activates the relay for the length of the time defined by Timer or until the alarm is acknowledged. Open Alarm count activates the relay for the length of the time defined by Timer or until the alarm is cleared from the console. In Alarm Count activates the relay for the length of time defined by Timer or until the alarm returns to normal. Total Alarm Count activates the relay or the length of time defined by Timer when an alarm occurs.
    Alarm Count Reports the number of alarms for the configured count type that activated the relay.
    Relay Value Indicates if the output relay is on (true) or off (false).
    Timer Reports the maximum amount of time that the relay is energized.