Alarm history Summary window

This window displays detailed information for a single alarm history row.

Figure 77.   Alarm History Summary window
Image

You access this window from the main menu by clicking Reports > Alarm History, followed by selecting an alarm history record and clicking the Summary button (Image).

Alarm Details properties

Property Description
Timestamp Reports when the transition from normal occurred, triggering the alarm.
Uuid Reports the Universally Unique Identifier.
Source State Reports the alarm’s component state transition (normal to offnormal, fault or alert).
Ack State Reports if the alarm has been acknowledged or is yet unacknowledged.
Ack Required Indicates if an acknowledgment is required: true means it is required; false means an acknowledgment is not required.
Source Reports the ORD that created the alarm.
Alarm Class Reports the routing information for the alarm.
Priority Reports alarm priority from 1 to 150, where 1 is the highest priority.
Normal Time Indicates when the alarm condition returned to normal.
Ack Time Reports when the alarm was acknowledged.
User Reports several pieces of information about the system user who was logged in when the system generated the alarm, including: name, timezone, badge number and if the alarm has been referred up the management hierarchy (escalated).
Alarm Data Reports additional information about the alarm, including any message text configured for the alarm, the user, and abbreviated information about the component that generated the alarm.
Alarm Transition Repeats the source state.
Last Update Reports the last time the system updated this alarm information.