Alarm Console Info icons

These icons appear under the Info column in the alarm console. Color coding and symbolic images represent the state of each alarm.
  • Image A red alarm icon in the table indicates that the current state of the alarm source is offnormal and not acknowledged.
  • Image An orange alarm icon in the table indicates that the current state of the alarm source is alert and is not acknowledged.
  • Image A yellow alarm (gold) icon in the table indicates that the current state of the alarm source is offnormal but is acknowledged.
  • Image A green alarm icon in the table indicates that the current state of the alarm source is normal and not acknowledged.
  • Image A white alarm icon in the alarm history table indicates that the current state of the alarm source is normal and acknowledged.
  • Image A note alarm icon (it may be any color) in the table indicates that there is a note associated with the alarm.
  • Image A link icon in the table indicates that the alarm has a link associated with it. When an alarm displays this icon, the Hyperlink button is also active.
  • Image A video alarm icon may display if video is available with the associated alarm. If included, this graphic appears at the left end of the alarm record row.
  • Image An optional icon may display if it is setup in the alarm properties. If included, this graphic appears at the left end of the alarm record row.