Provisioning requires a connection to each remote platform/station. For each NiagaraStation in the client station’s NiagaraNetwork, you must confirm the port and enter the corresponding platform daemon credentials of its host. The simplest way to do this
is by using either the Station Manager or Provisioning Manager views.
Prerequisites: All platform/stations to be provisioned are running. Each has its own signed server certificate recognized
by the client station for server authentication.
- In the Nav tree, expand , right-click NiagaraNetwork and select .
The
Provisioning Manager opens.
Each row in the table represents a connection to a remote server platform/station.
- Select one or more (a group) of stations and click Edit.
The system opens an
Edit window.
- Enter platform connection credentials, and, if using a non-default port address, change the port from the default port 5011
to the port number used and click OK.
These platform credentials and port should be the same credentials and port you use when you open a platform connection directly
to each remote host.
Upon the next monitor ping of the host’s platform daemon, its Station Run State should change from Unknown to Running and the station’s Platform Connection extension should now have a status of ok.
- To confirm the platform connection immediately, right-click the station’s Platform Connection extension and click .
- Confirm that the station, as shown in the Provisioning Manager, has a platform status of ok.
- To test the validity of the credentials, right-click the station row and click .
Repeat this procedure for each NiagaraStation listed in the Station Manager.