To access this view, expand and click .ProvisioningNwExt. To open the job steps window, click
and double-click Backup Stations or select Backup Stations and click OK. The Set Property window opens. Enter the properties mentioned below and click OK. This adds the job step component in the top pane (Provisioning steps to run) of the Niagara Network Job Builder or the Niagara Network Prototype View. Running this step creates a new platform account and remove default platform account.
| Property | Value | Description |
|---|---|---|
| Use NEQL | true or false (default)
|
Turns on (true) and off (false) the use of a NEQL query to identify the property to update.
|
| Target ORD | ORD | Selects one of seven choosers to identify the property. |
| Property Name | read-only | Reports the name of the selected property. |
| Property Type | two drop-down lists | Select any type registered with the
|
| Add if Missing | true or false (default)
|
Adds the property at the slot path. |
| Unique Value per Station | true or false (default)
|
Indicates if the updated property in each station should have the same value false or a unique value (true).
|
| Property Value | text | Contains the value. The editor for this value changes based on the selected Property Type.
You can set individual values if the |