This component is available in the bacnetAws palette, bacnetOws palette, and the bacnet palette.
To access these properties, expand and double-click SVO.
In addition to the common properties (Status and Fault Cause), this component has these properties.
| Property | Value | Description |
|---|---|---|
| Poll Frequency | drop-down list (defaults to Normal)
|
References the On Demand Poll Scheduler rates under the NiagaraNetwork’s History Policies container slot.
Configures how often this type of poll occurs. |
| Object Id | drop-down list and number (from 0 to 4194302) |
Identifies each device and component by the type of entity (
Object Id) combined with a unique Instance Number.
For devices (controllers, instruments, meters, etc.), |
| Object Name | text in the format name.name.name.name (default includes the entire component path in the station using period (“/) delimiters between parent.child levels) |
Identifies a BACnet object. This name should be unique within this specific device.
For components, this name includes the entire component path under the station’s Config using period (.) delimiters between parent.child levels. This enforces (externally) the BACnet requirement for unique names for all objects in a device. For a proxy point, this is the default name in the station. You can shorten or edit |
| Object Type | drop-down list of BACnet objects |
Reports the type of object.
|
| Node Type | drop-down list, defaults to unknown |
Classifies a BACnet object (node) as:
|
| Subordinate List | additional properties | Refers to the structured view objects, which are available to other structured view objects. |