To access these properties in a Supervisor station, expand the BACnet network and device, double-click the Trend Logs folder (
) and expand the BacnetEventLogImport component. If no import component is present, open a bacnetAWS palette, expand , and drag a BacnetEventLogImport component to the Trend Logs folder.
In addition to the common properties (Status, Enabled and Fault Cause), this component has these properties.
| Property | Value | Description |
|---|---|---|
| Execution Time | multiple properties |
Configures the frequency with which data are imported from a remote trend log (or trend log multiple) into a history (or histories).
Data import may occur at regular intervals (
Interval), Daily or when manually requested (Manual).
|
| Last Attempt | read-only |
Reports the date and time of the last attempted execution.
|
| Last Success | read-only |
Reports the last time the system failed to perform this function. Refer to
Fault Cause for details.
|
| Last Failure | read-only timestamp |
Reports the last time the station successfully performed this function.
|
| History Id | read-only | Displays a combination of the station name and history name. |
| On Demand Poll Enabled | true (default) or false |
Enables and disables polling of both local history sources and history imports for live data. The reported data appear on history charts and in history table views. |
| On Demand Poll Frequency | drop-down list | Configures how often this type of poll occurs. |
| Config Overrides, capacity | drop-down list (defaults to Unlimited)
|
Defines the maximum number of history records allowed in the associated table.
|
| Config Overrides, fullPolicy | drop-down list (defaults to Roll)
|
Defines what happens if
Capacity is set to Record Count and the specified record count is reached.
Full policy has no effect if |
| Object Id | drop-down list and number (from 0 to 4194302) |
Identifies each device and component by the type of entity (
Object Id) combined with a unique Instance Number.
For devices (controllers, instruments, meters, etc.), |
| Local History Name | read-only | Reports the name of the local history component. |
| Local History Name Format | text, BFormat (Baja Format) syntax (defaults to %name%, which recreates the BACnet name of the trend log object) or a combination of text and BFormat.
|
Defines the format string script for returning a local history. This is the name of the history initially created and populated
by the trend log data and includes, typically, the name of the BACnet device component and the BACnet trend log object.
For example: %parent.parent.displayName% %name% could define the name of a VAV fan: J7Bnet BldgA_VAV1_Fan. You can modify the default BFormat with other BFormat scripting. You could enter static text for the history nameāor, some combination of static text and valid BFormat scripting text. In the case of trend log multiples (BacnetTrendLogMultipleImport), the default |
| Reference Time | hours, minutes, seconds | Defines the timestamp the system uses to include records in the trend log. |
| Max Records Per Request | 0 (default) to max |
Defines the maximum number of records that can be archived in this trend log. The Framework asks for 10 records per request. |
| Always Request By Reference Time | true or false (default)
|
Configures if the driver should always use the
Reference Time to request records.
|
| Last Sequence Number Processed | number | Defines a maximum record number to process. |
| Local History Names | read-only | Reports the name of the local history component. |