Bacnet Multi State Input Descriptor (ServerMSIDesc)

This component exposes an EnumPoint as a BACnet Multi-state Input object. You use the Bacnet Export Manager view of the BACnet Export Table to add, edit, delete, and access exported components.
Figure 138.   Bacnet Multi State Input Descriptor properties
Image

You use the Bacnet Export Manager view of the Bacnet Export Table to add, edit, delete, and access exported components.

In addition to the common properties (Status and Fault Cause), this component has these properties.

Property Value Description
Event Detection Enable true (default) or false
Turns detection of an input event on (true) and off (false) for analog, binary and multi-state descriptors.
Bacnet Status Flags read-only indicator and check boxes
Configures four status flags for BACnet. These options are available to enable detection of specific status conditions.
Point Ord ord (defaults to null)
Defines the ORD (address) for the point.
Object Id drop-down list and number (from 0 to 4194302)
Identifies each device and component by the type of entity (Object Id) combined with a unique Instance Number.

For devices (controllers, instruments, meters, etc.), Instance Number must be unique within the BACnet internetwork. For components (points, schedules, analog inputs, files, groups, multi state inputs, etc.), it must be unique within the device.

Object Name text in the format name.name.name.name (default includes the entire component path in the station using period (“/) delimiters between parent.child levels)
Identifies a BACnet object. This name should be unique within this specific device.

For components, this name includes the entire component path under the station’s Config using period (.) delimiters between parent.child levels. This enforces (externally) the BACnet requirement for unique names for all objects in a device.

For a proxy point, this is the default name in the station.

You can shorten or edit Object Name, however, each Object Name must be unique among all server descriptors under the Export Table.

Reliability read-only
Provides information when an error interrupts communication with a device.

No Fault Detected indicates that things are OK.

Unreliable Other indicates that the exported BACnet object appears in fault. This might happen, for example, if the source (exported) component is a proxy point under some other driver, and device communications are down or if the point has been disabled.

In this case, the BACnet export descriptor retains a status of ok.

Description text
Provides additional information, which could include the camera’s geographical location or other unique information.
 NOTE: After creation (adding) BACnet file descriptors, note that each descriptor also has additional properties accessible in its property sheet, along with those seen in the New and Edit windows.  
Notify Type (optional) Alarm (default) or Event
Indicates if the notification is from an alarm or an event. This property applies if the source component has an alarm extension.
Device Type (optional) text only for some object types (Analog Input, Analog Output, Binary Input, Binary Output, Multi-state Input, Multi-state Output)
Defines the type of physical input or output. This might apply mostly to exported Ndio points where each point corresponds to a physical device.