Bacnet Boolean Trend Log Ext (bacnet-BacnetBooleanTrendLogExt)

This extension creates a history for the StatusBoolean out value of a component using COV or a defined interval.

You can export the history created by this extension as a fully-compliant BACnet trend log object.

 NOTE: This single extension applies to both COV and Interval data collection and may be used in place of the deprecated COV and Interval Trend Log Extensions for this data type. 
Figure 85.   Bacnet Boolean Trend Log Ext properties
Image

To access these properties, expand Config > Drivers > BacnetNetwork > BacnetDevice > Trend Logs > BacnetLogExtensions and double-click the BacnetBooleanTrendLogExt.

In addition to the common properties (Status, Fault Cause and Enabled), this component has these properties.

Property Value Description
Active Period, Start Time Date and Time selectors
Configures when to start the log.
Active Period, Stop Time Date and Time selectors
Configures when to stop the log.
Active read-only
Indicates the current state of the trend log based on the Active Period.

true indicates the log is active.

false indicates the log is no longer active because the current time is outside the Active Period.

History Name BFormat string (defaults to %parent.name%)
Defines a pattern for deriving the name of the history created by this extension. It can be static text or a simple pattern that allows the actual history name to be derived from the context. The default value (%parent.name%) sets the history name in the Id to the name of the parent of this extension. Changes to this property cause the format to be reapplied and the history Id in the history config is to be updated.
History Config additional properties
Serves as a container for sub-properties used to configure the attributes of the history record stored in the History space.

A separate topic documents these properties.

Last record read-only
Stores a copy of the most recent record successfully appended to the history for this extension.
Interval hours, minutes, seconds
Controls data collection behavior for this Trend Log component.

If the Interval value is set to 0, the driver collects trends when a change of value (COV) on the parent point occurs. The subscription lifetime is equal to twice (2x) the value of the COV Resubscription Interval property.

If the Interval value is set to any number greater than 0, the driver collects trend data at the specified time interval.

Total Record Count read-only
Indicates the total number of records collected by the Trend Log object since creation. When the value of Total Record Count reaches its maximum possible value, the next value it takes is zero.