Alarms (bacnet-BacnetAlarmDeviceExt)

Each BacnetDevice has an Alarms device extension. This extension applies to BACnet event notifications (alarms) sent to the station from a device.
Figure 62.   BacnetAlarmDeviceExt (Alarms) properties
Image

One way to view these properties is to expand BacnetNetwork > BacnetDevice followed by double-clicking the Alarms node in the Nav tree.

Property Value Description
Alarm Class drop-down list
Defines alarm routing options and priorities. Typical alarm classes include High, Medium and Low. An alarm class of Low might send an email message, while an alarm class of High might trigger a text message to the department manager.
Last Received Time read-only Reports the date-timestamp of the last BACnet event notification received from the device.
Niagara Process Id integer Specifies a process ID, which needs to match the BACnet process identifier used to send notifications to this client station. The default value is 0.