These icons appear under the Info column in the alarm console. Color coding and symbolic images represent the state of each
alarm.
A red alarm icon in the table indicates that the current state of the alarm source is offnormal and not acknowledged.
An orange alarm icon in the table indicates that the current state of the alarm source is alert and is not acknowledged.
A yellow alarm (gold) icon in the table indicates that the current state of the alarm source is offnormal but is acknowledged.
A green alarm icon in the table indicates that the current state of the alarm source is normal and not acknowledged.
A white alarm icon in the alarm history table indicates that the current state of the alarm source is normal and acknowledged.
A note alarm icon (it may be any color) in the table indicates that there is a note associated with the alarm.
A link icon in the table indicates that the alarm has a link associated with it. When an alarm displays this icon, the Hyperlink button is also active.
A video alarm icon may display if video is available with the associated alarm. If included, this graphic appears at the
left end of the alarm record row.
An optional icon may display if it is setup in the alarm properties. If included, this graphic appears at the left end of