Nrio16PointFolder. The Nrio16 Point Manager is the default view on both types of these components. To view, right-click the Nrio16Points extension or Nrio16PointFolder and select , or simply double-click the component.
Columns in the Discovered and Database panes of this view are summarized below.
The Discovered pane of this view has the following available columns:
Shows a default name for each available IO point, using format AbbrevIoTypeTerminalNumber, for example, ui4, ao2, and so on.
Type of I/O for each point, such as Universal Input, Relay Output, or Analog Output.
Equals the hardware I/O terminal number for that IO type, for example 1 for UI 1 or AO 1.
Has a value only if the IO point is already represented in the station’s database, formatted as ParentName.NrioProxyPointName. For example, Onboard_IO.AHU_status or Inputs1.ReturnAir
The Database pane of this view has the following available columns:
Component name of the Nrio proxy point.
Base control point type, such as BooleanPoint, NumericPoint, NumericWritable.
Equals the hardware I/O terminal number for that IO type, for example 1 for UI 1 or AO 1.
Descriptor for type of UI (if applicable), blank if point is an AO or DO. For example, DI_Normal, AI_Resistive, AI_0to10_Vdc, DI_High Speed, and so on.
Conversion type used in Nrio ProxyExt, such as Linear, Default, 500 Ohm Shunt, Thermistor Type3, and so on.
Current out value and status of proxy point.
Facets information string for proxy point, including units, precision, and min/max value for numeric points, or true/falseText for boolean points.