In the dialog, enter the sensor’s non-linear response curve (shown below). Configure this point’s facets to have units: “illuminance,” “lux” (lx), and the same units in the point’s Linear Calibration Ext.
|
Ohms |
Lux |
|---|---|
|
3000 |
800 |
|
3200 |
700 |
|
3500 |
600 |
|
4000 |
500 |
|
4200 |
450 |
|
4600 |
400 |
|
5000 |
350 |
|
5500 |
300 |
|
6100 |
250 |
|
6900 |
200 |
|
8200 |
150 |
|
10200 |
100 |
|
10900 |
90 |
|
11600 |
80 |
|
12400 |
70 |
|
13300 |
60 |
|
14400 |
50 |
|
15800 |
40 |
|
17700 |
30 |
|
20300 |
20 |
|
30000 |
0 |