ResistiveInputPoint

A ResistiveInputPoint is a NumericPoint with NrioResistiveInputProxyExt. It configures a UI to read a resistance from 0 to 100,000 ohms. Default configuration provides ohms. If other units are needed, select conversion type of either Linear (for linear response) or Generic Tabular, if non-linear.
 
NOTE: Universal inputs (UIs) are optimized for resistive temperature sensors in 10K ohm range. Any temperature sensor far outside this range, for example a 100 ohm or 1K ohm type, will have poor resolution—and thus be unusable! In this case, install a compatible transmitter that provides a linear 0-to-10V or 4-to-20mA signal, and use a VoltageInputPoint instead.
 

The ResistiveInputPoint is pre-configured with a linearCalibration extension, to allow for offset correction.

Figure 26.   Nrio Resistive Input Point
Image

The ResistiveInputPoint’s Proxy Ext contains only common Nrio Proxy Ext properties. Among these, note that the read-only “Device Facets” property is preset to ohms.