Quick start

Follow these steps to get started with CCN driver.
Prerequisites:

You are working in Workbench running on a PC and are connected to a remote station.

  1. Open the ccn palette, copy the CcnNetwork component to the Drivers node, right-click the CcnNetwork node and click Views > Ccn Network View.
    The Ccn Network View (a property sheet) opens.
  2. Update at least these properties and click Save.
    • Bus and element ranges: First Bus No, Last Bus No, Low Elem No and High Elem No for the devices to discover.
    • The driver's Bus Address and Elem Address (typically 230-238).
    • Comm Port.
     NOTE: On a controller, configure only the available ports. 
  3. Add devices by opening the Ccn Device Manager view, click Discover, then select and add the CCN device(s).
  4. Once device(s) are added, double-click the Points folder, which is available under CcnDevice.
    The Ccn Table Manager view opens.
  5. To discover the table groups available under a device, click Discover, then select and add the groups to the database.
    The driver adds the group tables and categorizes them.
  6. Once the table group(s) are added, navigate to a table (PIC, POC or FID) under a table group and discover points.