Designating a station as a CCN time broadcaster

Many CCN devices may broadcast information over the network, such as the time of day or point values like outdoor air temperature. This procedure configures a device to broadcast the time.
Prerequisites: You are connected to the remote station.
  1. To access CcnNetwork properties, expand Config > Drivers and right-click CcnNetwork. From the menu, select Views > Ccn Network View.
  2. Set the Time Broadcaster property to true and click Save.
  3. To enable time broadcasting, right-click the CcnNetwork and select Actions > Time Broad Casting.