Creating and configuring a CCN object

You can only add a CCN object under a CcnPicTable or CcnDataTable using the Ccn Fid Table Point List Manager.
Set Command, Override Command, and Auto Command are actions that you can find on theCcnObject depending on its type. The Set command writes a non-forcible Ccn object.
Perform the following steps:
  1. To perform this command, add the CcnObject to the station.
  2. Right-click CcnObject. From the menu, select Actions > Set command. You can issue this action using the Point List Manager or Wire Sheet view.
    If you set the value within the limits, the driver writes the new value to the field device.
  3. The Override command forces a Ccn Output object on if it is a discrete point type with a value of 1, and an active text as defined by the one’s value of the Discrete Text Offset text pair. This command forces the object off if it has no value (0) with an inactive text as defined by the no value (0) of the Discrete Text Offset text pair. The CCN driver manages two force levels (level 4 is used for commands, level 8 is used for links) and the auto level (0). The command level force is the highest priority available from the driver.
    If the CcnOutput object is a discrete point type, the command opens a combo box, with Force On (Discrete on Text) and Force Off (Discrete off Text) options.
  4. If you select either of these commands, a Force command will be issued. After the Force command is successfully completed, the value field(s) of the Point Entry and CcnOutput object reflect the new value and the row in the Point List Manager view changes to the color lavender.
  5. To perform a point value Force command, add the Ccn object to the station database.
  6. Right-click the Ccn object. From the menu, select Actions > Override command.
    You can override a value using the Point List Manager or Wire Sheet view. Auto command removes the force level command on a CcnOutput object.
    After the Auto Command is successfully completed, the value field(s) of the Point Entry and CcnOutput object reflect a new value.
  7. To perform this command, add the CcnObject to the database.
  8. Right-click the CcnObject. From the menu, select Actions > Auto command.
    You can override a value using the Point List Manager or Wire Sheet view.