Prerequisites: The parent table group exists.
- To open a Ccn Table Manager, expand and double-click the Points folder.
The Ccn Table Manager opens.
- To add a table to the group, click New. Select the type of table and click OK.
This adds the CcnTable to the CCN device.
- Double-click the table. Set the
Table Type and Table Instance properties to their actual values in decimal, not hex and click Save.If the table type is 501H (for Fid IO points), set the instance to 1.
If the table type is CcnDataTable or CcnDataTableWithTimeSchedule, also set the Block Number.
- Do one of the following:
- Click (menu bar under command).
- At the bottom of the view, click Fetch.
The driver retrieves additional table information and builds it to the point list.
NOTE: The table name “SPSCHPOC” does not support the manual addition of a table and fetching.