Option module and capacity considerations

The controller supports a maximum total of four option (expansion) modules in certain combinations.

If you use two RS485 option modules, you are limited to one additional non-RS485 module (LON or RS-232) for a total of three modules. The following figure shows some example combinations.

Figure 2.   Valid module combinations
Image

Maximum option modules supported by protocol

Expansion Module Max Components
NPB-8000–LON 4
NPB-8000–232 4
NPB-8000–2X-485 2

Separate maximum limits may be defined in the controller’s license, such as total number of networks, devices, and integration points (capacity licensing).

Maximum wired field bus integrations

Protocol Maximum Description, Option Module
RS485 7 Two via onboard RS485, four via two Dual RS485 option modules (2 ports each), plus one via LON or RS-232.
Lonworks FTT-10 4 Four LON option modules (1 port each module)
RS232 4 Four RS-232 option modules (1 port each module)

The maximums above do not reflect combinations of wired field bus integrations. Two examples:

  • Two RS485 modules (via onboard RS485), two Lonworks FTT-10 (2 LON modules), two RS-232 modules. In these configurations, the maximum number of option modules (4) are installed.
  • Four RS485 (two via onboard RS485, two from a single Dual RS485 module), two Lonworks FTT-10 (two LON modules). In this case, three (3) option modules are installed.
Future option module types may have additional maximum limits within the 4–total option per controller limit.