In the PupNetwork property sheet you must define several parameters for communications.
To set the PUP network communications parameters
To set the communications parameters for a PupNetwork:
Right-click the PupNetwork and select ->.
The Property Sheet appears.
Expand the Serial Port Config slot.
Set the properties for the JACE serial port used, where defaults are:
Port Name: none — Enter the JACE port being used, like COM2 or COM3.
Baud Rate: Baud9600 — Or choose different from selection list.
Data Bits: Data Bits8 — Or choose different from selection list.
Stop Bits: Stop Bit1 — Or choose different from selection list.
Parity: none — Or choose different from selection list.
Flow Control Mode: none — Or choose different using checkbox.
You must determine the setup of the PUP serial network to correctly set the baud rate, data bits, stop bits, parity, and flow control settings.
Set the Unit Number property value to assign an address to the Niagara network node. The PupNetwork behaves as a master device on the PUP network, and as such must have an address in order to send and receive messages from the network.
Expand the Token Pass Config slot and edit properties as needed. For more details, see Token Pass Config.
Click the button.
For further details on the PupNetwork, see PupNetwork.