accessDriver-AccessNetwork

This component manages and configures the access network.
Figure 75.   AccessNetwork properties
Image

To open this Property Sheet, right-cick the AccessNetwork node in the Nav tree and click Views > AX Property Sheet.

In addition to the standard properties (Status, Enabled, Fault Cause, Health, Alarm Source Info, Monitor, Tuning Policies and Poll Scheduler), these properties configure this component:

Property Value Description
Retry Count number Configures how many times to repeat a network read request, if no response is received before the response timeout interval elapses.
Response Timeout hours minutes seconds (defaults to .500 seconds) Configures the length of time before the system times out when interrogating a device on the network. Start by setting this value to a large number, such as 40 seconds. Then, reduce it depending on the number of devices and on the discovery performance.
 NOTE: Baud rate also impacts performance especially if each device has a different baud rate. 
Port Name COM2, COM3 Defines the communication port to use: none, COM2 or COM3.
Trunk number Specifies which trunk the port is connected to.

Each RS-485 connection is called a trunk. If your network has multiple RS-485 trunks, a separate network and remote I/O module are required to support each.

Baud Rate read-only Defines communication speed in bits per second.
Sdi Value Config additional properties Sdi (Sensor Digital Interface) configures input from the sensor.

Refer to Sdi Value Config.

Push To Points true (default) or false Enables (true) and disables (false) the sending of data to points.
Output Failsafe Config read-only seconds (defaults to 8) Configures timeout values. Refer to Output Failsafe Config.
Unsolicited Msg Count read-only Reports the number of unexpected messages.
Unsolicited Process Time read-only Reports the amount of unexpected process time.
Unsolicited Message Rate read-only Reports the rate at which unexpected messages are being received.
Pushed Unsolicited Message Rate read-only Reports the rate at which unexpected messages are being sent.
Keypad Entry Time hours minutes seconds (defaults to 10 seconds) Configures an amount of time.
Show Results Time hours minutes seconds (defaults to 2 seconds) Configures an amount of time.
Validation Timeout hours minutes seconds (defaults to 10 seconds) Configures an amount of time.
Base Board Avail Version read-only Reports a version number.
Remote Reader Avail Version read-only Reports a version number.
Remote Io Avail Version read-only Reports a version number.
Network version read-only Reports a version number.

Sdi Value Config

Figure 76.   Sdi Value Config properties
Image
Property Value Description
Cut Value number (defaults to 3412) Defines a value for the cut voltage parameter on the network.
Open Value number (defaults to 2047) Defines a value for the open voltage parameter on the network.
Closed Value number (defaults to 682) Defines a value for the close voltage parameter on the network.

Output Failsafe Config

Figure 77.   Output Failsafe Config properties
Image
Property Value Description
Comm Loss TImeout seconds (defaults to 8 seconds) Defines a number of seconds after which the station stops sending data, thereby indicating a loss of communication signal.
Startup Timeout seconds (defaults to 180 seconds) Defines a number of seconds after which the startup times out.