Enabling and disabling SRAM support in the DataRecoveryService

SRAM support is provided by the DataRecoveryService, a platform service that applies to SRAM-equipped JACE controllers.

You are using Workbench and are connected to a remote station.
  1. In the Nav tree, expand the station’s Services > PlatformServices, and double-click DataRecoveryService.
    The Data Recovery Service Editor window opens.

    By default, the Service Enabled property is true. This is appropriate since the controller has no backup battery installed.

  2. If a battery-less controller is powered from a battery-backed UPS, you could also choose to set Service Enabled to false.
    If you set Service Enable to false, the DataRecoveryService no longer records runtime database changes to SRAM but depends entirely on its backup battery to preserve station data upon a power loss!
  3. To write the configuration to the host platform, click Save.
    You are prompted to reboot now to apply the changes.
  4. To reboot with the change in the DataRecoveryService (disabled or enabled) made effective, click Yes.