Testing the database connection

This procedure applies to any type of rdb Database.
Prerequisites: You are working in Workbench
  1. Right-click RdbmsNetwork > RdbmsDatabase Device Extension in the Nav tree, and click Actions > Ping.
    If a valid connection to the database is made, the Health property displays {Ok}.
  2. If the Health property displays {Fail}, a connection is not made and you should examine the Last Fail Cause property for details.