Identifying a device using its service pin

If you are unable to discover nodes that are physically connected to the station, they may be configured on a different domain. Use the following method to gain access to a device by use of its Lonworks Service pin.
  1. Right-click the network and click Views > Lon Utilities Manager.

    The Lon Utilities Manager view opens.

  2. Near the bottom, click the lower-left drop-down control (command menu) and select Identify.
  3. Click the drop-down Identify control to the right (command submenu) and select Service Pin.
     NOTE: For this command, the selected Lon device makes no difference (Local Lon Device, other). 
  4. Click the Execute  button (Image).

    The view updates to show a timestamp with the message Waiting on service pin below.

  5. At any connected Lon device, press its service pin.
The Lon Utilities Manager view shows the device’s domain table, including the domain length (Domain Len) and the ID for the device. If the device is configured on something other than the zero-length domain (Domain Len is not 0), you must configure the network’s working domain to match.

By default, when expressly listening for a service pin message from the Lon Utilities Manager view, you have 300 seconds of listen time for a service pin before the utilities manager cancels the wait period.

You configure both the Domain Id and the Service Pin Wait under the Lon network’s LonNetmgmt container.