Command: Data Structs, Subcommand: Read Only Structure, and click Execute.Current Size property reflects the changes to buffer count or size. To be applicable, modifications cannot exceed the size shown in the
Original Size property—that is, Current Size must be less than or equal to Original Size. For example, to increase a buffer size, you may need to decrease its count.
The system does not automatically write message buffer changes saved on the BufferParam’s Property Sheet to the Neuron chip in the Local Lon Device.
Current Size less than or equal to Original Size, and click Save.Current Size is greater than Original Size, the job throws an exception, and writes no changes to the Neuron chip.