Simultaneous_Heat_Cool

This algorithm analyzes trend data and returns a true result, indicating that an exception existed, if the building was occupied, the supply fan command was on, the supply fan status was on, the heating valve position or the heating valve command was greater than 0%, and the cooling valve position or cooling valve command was greater than 0% for 15 minutes. A false result indicates that nothing was wrong.

Input ORDs

slot:/Algorithm/English/Simultaneous_Heat_Cool

slot:/Algorithm/Metric/Simultaneous_Heat_Cool

Wire sheet

Figure 41.   Fragment of the Simultaneous Heat Cool algorithm wire sheet
Image