Low_Chilled_Water_Temp

This algorithm evaluates trend data and returns a true result, indicating that an exception existed, if a chiller was commanded on, the chiller status (feedback) indicates it was running, and the chilled water supply temperature was greater than 1 degree Fahrenheit below the chilled water supply water temperature setpoint for 30 minutes. A false result indicates that nothing was wrong.

Input ORD

slot:/Algorithm/English/Low_Chilled_Water_Temp

slot:/Algorithm/English/Low_Chilled_Water_Temp

Wire sheet view

Figure 23.   Low Chilled Water Temp algorithm
Image