Chilled_Water_Mixing

This algorithm evaluates trend data and returns a true result, indicating that an exception existed, if a chiller received the command to run, it was on line, and the chilled water supply temperature minus the chilled water supply temperature was less than three degrees Fahrenheit for 30 minutes. A false result indicates that nothing was wrong.

ORDs

slot:/Algorithm/English/Chilled_Water_Mixing

slot:/Algorithm/Metric/Chilled_Water_Mixing

Wire sheet view

Figure 3.   Chilled Water Mixing algorithm