This algorithm compares steam water usage this month with usage from the previous month. It produces a true result, indicating
that an exception exists, if the total steam water usage for this month is greater than the total monthly usage for the previous
month by more than 5%.
Input ORD
slot:/Algorithm/English/Steam_Water_Usage_Plus_5_PC_of_last_Monthslot:/Algorithm/Metric/Steam_Water_Usage_Plus_5_PC_of_last_Month
The algorithm uses two rollup blocks, numeric constant, calculation and switch block to calculate the result.
Figure 40. Water usage plus 5 percent of last month wire sheet