This algorithm evaluates trend data collected from an AHU unit. It returns true if the facility was occupied, the command
to turn the supply fan on was given, the supply fan was on, and the position of the damper was more than 95% open for 30 minutes.
A false result indicates that nothing was wrong.
ORDs
slot:/Algorithm/English/Prolonged_100_Percent_VAV_Damperslot:/Algorithm/Metric/Prolonged_100_Percent_VAV_Damper
Algorithm
Figure 30. Prolonged 100% VAV Damper algorithm