Low_Outside_Air_Intake

This algorithm evaluates trend data collected from an AHU unit. It returns a true result if four conditions are met for an hour. Otherwise, it returns false. The four conditions are: was occupied, the command had been given to turn the supply fan on, the supply fan was on, and the outside air flow coming in was less than 90% of the outside airflow setpoint. A false result indicates that air coming in from the outside was normal.

ORDs

slot:/Algorithm/English/Low_Outside_Air_Intake

slot:/Algorithm/Metric/Low_Outside_Air_Intake

Wire sheet

Figure 25.   Low Outside Air Intake algorithm
Image