EconomizerNotRunning-EnthalpyBased

This algorithm returns true if, when a room or building is occupied, the economizer is off and the outside air enthalpy is less than the sum of the economizer setpoint and the return air enthalpy for more than 30 minutes.

Input ORD

slot:/Algorithm/English/EconomizerNotRunning-EnthalpyBased

slot:/Algorithm/Metric/EconomizerNotRunning-EnthalpyBased

Wire sheet view

Figure 10.   Economizer not running, enthalpy-based wire sheet
Image