This algorithm returns true if, when a room or building is occupied, the economizer is off and the outside air temperature
is lower than the economizer setpoint for more than 30 minutes.
Input ORD
slot:/Algorithm/English/EconomizerNotRunning-TempBasedslot:/Algorithm/Metric/EconomizerNotRunning-TempBased
Wire sheet view
Figure 11. Economizer not running, temperature-based wire sheet