When an AHU is warming up in the morning, the outside air damper should not be on or open more than 5%.
This algorithm returns an exception if two conditions are met:
- An AHU is in warm-up mode and
- The outside air damper command is on or the outside damper position is more than 5% open.
Input ORD
slot:/Algorithm/English/Damper_Open_During_Warmupslot:/Algorithm/Metric/Damper_Open_During_Warmup
Wire sheet view
Figure 9. Damper open during warm-up wire sheet