Damper_Open_During_Warmup

When an AHU is warming up in the morning, the outside air damper should not be on or open more than 5%.

This algorithm returns an exception if two conditions are met:

  • An AHU is in warm-up mode and
  • The outside air damper command is on or the outside damper position is more than 5% open.

Input ORD

slot:/Algorithm/English/Damper_Open_During_Warmup

slot:/Algorithm/Metric/Damper_Open_During_Warmup

Wire sheet view

Figure 9.   Damper open during warm-up wire sheet
Image