The OrionAlarmService component is available in the alarmOrion palette.

In addition to the standard properties (Status, Enabled, and Fault Cause), this component provides these properties.
To access, expand and right-click .
| Type | Value | Description |
|---|---|---|
| Alarm Db Config | 1–250,000 records | Defines the number of alarm records to store in the histories database. When the capacity is reached, newer alarm records overwrite the oldest records. |
| Alarm Class | drop-down list (defaults to Medium) |
Defines alarm routing options and priorities. Typical alarm classes include
High, Medium and Low. An alarm class of Low might send an email message, while an alarm class of High might trigger a text message to the department manager.
|
| Master Alarm Instructions | additional properties | Click the Add creates a new instruction. Edit edits a existing instruction. Remove deletes the selected instruction from the list. Move Up/Down changes the order of the instructions in the list. |
| Coalesce Alarms | true or false |
When
NOTE: If sequences or notifications in the Supervisor station are triggered by alarms, you should not coalesce alarms. You do not
coalesce alarms if you may need to document security incidents.
|
| Database | ord | Provides the ord path to the database that is used by the Orion Alarm Service. |
| RdbAlarmDatabaseConversion | additional properties | Configures additional parameters to convert a RDBMS to an Orion database. |