The alarm class:

| Property | Value | Description |
|---|---|---|
| Ack Required | true or false |
Indicates if the alarm must be acknowledged (
true) or not (false).
|
| Priority [on-call contact] | 1–255 for each transition, default: 255; %priority% on a report |
Specifies the order in which the OnCallService sends alarm notifications to the OnCallContact. Colors graphically identify alarm priority levels. You set up Priority levels using the alarm options window. The contact
with the lowest number (highest priority) receives notification first. An alarm that is not acknowledged within the designated
time is forwarded to the next contact in the list.
NOTE: Contacts may share the same Priority number. The OnCallService sends an identical notification to all contacts that have the same priority number
|
| Total Alarm Count | read-only |
Displays the total number of alarms assigned to the
Alarm Class from all sources.
|
| Open Alarm Count | read-only |
Displays the current total number of alarms that are unacknowledged and normal or unacknowledged and an alert.
|
| In Alarm Count | read-only |
Displays the total number of alarm conditions.
|
| Unacked Alarm Count | read-only |
Displays the total number of unacknowledged alarms.
|
| Time Of Last Alarm | read-only |
Displays when the system generated the last alarm assigned to this
Alarm Class.
|
| Escalation Level(n) Enable | true (default) or false and check box, where n is 1, 2 or 3
|
Turns this escalation level on (
true) and off (false).
|
| Escalation Level(n) Delay | hours and minutes; one minute is the smallest increment you can set for this property. |
Sets the time between alarm generation and escalation. It is not the time between escalation levels. Set a time to allow an
unacknowledged alarm to remain unacknowledged before you escalate it to the next level.
|