Actions on this component include: Route Alarm
| Property | Value | Description |
|---|---|---|
| Time Range | Start Time and End Time [hours of the day (defaults to 24 hours)] |
Specify when during the day (start and stop times) this recipient receives alarms.
|
| Days of the Week or Days of Week | check box |
Specifies the days of the week to include.
|
| Transitions | drop-down list |
Selects which alarm transitions to display in the console. Only those transitions selected display although the station saves
all transitions in alarm history.
Options are: |
| Route Acks | true (default) or false |
Enables (
true) and disables (false) the routing of alarm acknowledgements to the recipient. The framework does not route trap (event notification) acknowledgements
if you select false.
|
| Enabled | true or false |
Activates (
true) and deactivates (false) use of the object (network, device, point, component, table, schedule, descriptor, etc.).
|
| Phone Numbers | phone number international format | Defines the recipient's telephone number. It must be in international format. |
| Body | 140 characters of text | Defines the message itself, which defaults to Source, Text and UUID. You may format the text for the SMS message within the body slot. |