Alarm Class Summary view

The alarm class summary provides a tabular presentation of data associated with all alarm classes that are assigned to the AlarmService.

As with other tables, you can show or hide columns and use other standard table controls and options that are provided in the Table Options menu. The Table Options menu is located in the top right corner of the table and the export toolbar icon is available on the toolbar.

Image
 NOTE: Double-click on any row in the view to change to the property sheet view of the alarm class that you clicked on. You can also use the popup menu to select a view. 
Column Value Description
Name text Identifies the alarm class.
Total number Displays the total number of alarms associated with the alarm class.
Open number Displays the total number of open alarms associated with the alarm class.
In Alarm number Displays the total number of alarms (points) for the alarm class that are currently in the alarm state.
Unacked number Displays the total number of unacknowledged alarms associated with the alarm class.
Last Alarm date and time Displays the timestamp of the last alarm associated with the alarm class.
alarm.Class.priority text Lists the priority of each alarm transition type, for example: “toOffnoamrl=1,” “toFault=60,” “toNormal=220,” and so on.
To Path String text Identifies, as a string value, the path to the alarm class.