Actions include Route Alarm.
| Property | Value | Description |
|---|---|---|
| Time Range | Start Time and End Time [hours of the day (defaults to 24 hours)] |
Specify when during the day (start and stop times) this recipient receives alarms.
|
| Days of the Week or Days of Week | check boxes |
Specifies the days of the week to include.
|
| Transitions | drop-down list |
Selects which alarm transitions to display in the console. Only those transitions selected display although the station saves
all transitions in alarm history.
Options are: |
| Route Acks | true (default) or false |
Enables (
true) and disables (false) the routing of alarm acknowledgements to the recipient. The framework does not route trap (event notification) acknowledgements
if you select false.
|
| To | email address | This is the email address of the email recipient (person who is to receive the emailed alarm). |
| Cc | email address | This is the email address of anyone that is to receive a carbon copy of the alarm. |
| Bcc | email address | This is the email address of anyone that should receive a carbon copy of the alarm, but whose name you do not want to display in the delivered email. |
| Language | two lower-case letters | This is the ISO 639 language code as two lower-case letters. For a list of codes, see the following: http://www.loc.gov/standards/iso639-2/langcodes.html |
| Email Account | drop-down list | Selects the email account to use for sending the alarm. |
| Subject | text (default:
)
|
Defines the alarm subject line. |