alarm-BooleanCommandFailureAlarmExt

This alarm extension generates an alarm when a BooleanPoint's or BooleanWritable's Out slot does not match a feedback value, which can be linked to other points, for more than timeDelay. It applies it to points with a status boolean output.

Algorithm properties

This property is unique to the BooleanCommandFailureAlarmExt.
Property Value Description