This alarm extension generates an alarm when a BooleanPoint's or BooleanWritable's Out slot does not match a feedback value,
which can be linked to other points, for more than timeDelay. It applies it to points with a status boolean output.
Algorithm properties
This property is unique to the BooleanCommandFailureAlarmExt.
| Property |
Value |
Description |
| Feedback Value |
true or false (default)
|
Provides FeedbackValue input property for linking. The status is not used by the algorithm.
|