Review the current drivers and applications running on the JACE controllers to be converted. See Driver and application support for details.If any drivers or applications are unsupported in
N4.0, but are critical to retain, you can opt to leave those controllers running
AX-3.8, and still integrate them with
Niagara 4
Supervisor station. However, you cannot integrate a
Supervisor at
AX-3.8 with
Niagara 4 JACE controllers.
NOTE: For any job that will have a
mix of
Niagara 4 and
AX-3.8 platforms, refer to the section
Wire compatibility.
Make an
N4.0 license request for all platforms to be migrated. You need confirmation that these licenses are ready before migrating the
platforms (
AX licenses do not work in
Niagara 4).In almost all cases, the calculated host ID remains the same. An exception is if, on a Windows platform, you are moving from
a 32-bit install to a 64-bit install (or vice versa), in this case, the host ID differs.
Be sure to archive the old
AX-3.8 license files as well.